CRS100

A fully self-contained low noise 100kW chiller package containing 2 individual Maneurop compressors giving 2 steps of capacity control. Designed for external (roof or ground level) use, the lightweight air-cooled CRS100 chiller arrives on-site ready for installation with integral pump, quick-connect flexible pipework and power point connections.
CRS 100 System Features
- Multi-compressor system to manage variable load conditions, offering minimal wear and tear
- 400 litre Thermal buffer tank to manage variable approach temperatures
- Fully weatherproof for external use
- LED panel for simple display control
Additional Features
- Low temperature versions to –30ºC
- Integral pump (400 I/m) enclosed within unit
- Heat pump version available
- 400 litre thermal buffer tank
- Additional units can be supplied in parallel
- Compressors housed in enclosed acoustic unit
Evaporator Data | |
Evaporator type | Tube & Thermal Buffer Tank |
Maximum Flow | 400 litres/min |
Maximum Pressure | 6 bar / 600 kPa |
Maximum Pressure Drop | 0.50 bar / 50 kPa |
Tank Size | 89 litres |
Standard Strainer | G.P. intake |
L x W x H | 1655 x 1060 x 1680 mm |
Operational Weight | 791 kg |
Equipment Data | |
Nominal Capacity | 100 kW |
Refrigerant | R22 |
No. Compressor / Circuits | 2 / 1 |
Compressor Type | Fully Hermetic Maneurop |
Capacity Steps | 2 |
Control System | Microprocessor |
Operating Temperature Range | 25ºC to –30ºC |
Physical Dimensions & Weight | |
Length (mm) | 2,200 |
Height (mm) | 1,900 |
Width (mm) | 900 |
Weight (kg) | 1,000 |
Water Connections | 50 mm / 2” BSP Female |
Electrical Data | |
Power Supply | 3 phase / 50Hz / 400v / No Neutral |
Power Input | 33 kW |
Running / Inrush Current | 58 amps / 115 amps |
Connecting Cforme Plug | 63 amp 5 Pin |
Recommended Cable Size | 4 x 20 mm2 |
Recommended Genset | 60KVA |
Optional Ancillary Supply | |
Connections: | Water Hose / Power Cable |
Glycol: | Monopropylene / Ethylene |
Heat Exchangers: | Brazed / Gasketed Plate |
CRS 100 Unit Full Load Sound Pressure | |
57dB(A) sound pressure level at 10 metres referred to open field conditions ISO 3744. |
Turn to the Rental Experts - Call + (65) 6261 0800
For more information contact us now on + (65) 6261 0800 or e-mail Rental.CRS@carrier.com